fixed installation flexible applications LiYCY(TP) 250V 5x2x0.25 mm

 Tip:Onclick the picture canbe zoom.

Application

data transmission cable, control and connecting cable predominantly for transmission of

analog and digital signals in process controlled facilities in measurement and control

technology for lossless transmission of data and signals. For fixed laying and flexible

applications with undefined cable routing and without tensile stress. Suitable for use in

dry and humid rooms. Outdoor use only with UV-protection, no laying underground.


Special Features

• twisted pairs

• largely resistant to acids, bases and specified types of oil

• free from lacquer damaging substances and silicone (during production)

• recommended for EMC-applications


Structure & Specifications

conductor material:bare copper strand

conductor class: acc. to IEC 60228 cl. 5; exception: 0,34 mm², stranded

(7 x 0,25 mm)

core insulation: PVC

core identification: acc. to DIN 47100 different colours

stranding: 2 cores twisted to a pair; pairs stranded in layers

protection against contact: plastic foil

shield: copper braid tinned; coverage approx. 85%

outer sheath: PVC

sheath colour: grey, RAL 7032

rated voltage: 250 V; peak-voltage on 0,14 mm²: 350 V; > 0,14 mm²:

500 V

testing voltage: on 0,14 mm² core/core: 2kV; core/shield: 1,2kV > 0,14

mm²: core/core: 2kV; core/shield: 1,5kV

conductor resistance: acc. to IEC 60228 cl. 5

insulation resistance: min. 20 MΩ x km

current carrying capacity: acc. to DIN VDE, see Technical Guidelines

capacity: core/core ca. 120 nF/km; core/shield ca. 160 nF/km

min. bending radius fixed: up to 12 mm Ø: 5 x d; up to 20 mm Ø: 7,5 x d; > 20 mm

Ø: 10 x d

min. bending radius moved: up to 12 mm Ø: 10 x d; up to 20 mm Ø: 15 x d; > 20 mm

Ø: 20 x d

operat. temp. fixed min/max: -30 °C / +80 °C

operat. temp. moved min/max: -5 °C / +70 °C

burning behavior: self-extinguishing & flame-retardant acc.to IEC 60332-1

standard: similar to DIN VDE 0812